Note On Adding Refrigerant
CAUTION
• Refrigerant charging must be performed after wiring, vacuuming and the leak test.
DO NOT exceed the maximum allowable quantity of refrigerant or overcharge the system.
Doing so can damage or impact the unit' s function.
• Charging with unsuitable substances may cause explosions or accidents. Ensure that the
appropriate refrigerant is used.
• Refrigerant containers must be opened slowly. Always use protective gear when charging the
system.
DO NOT mix refrigerants types.
Some systems require additional charging depending on pipe lengths. The standard pipe length
is 15m. The additional refrigerant to be charged can be calculated using the following formula:
Liquid Side Diameter
6.35(1/4")
(Total pipe length -
standard pipe length)
x15g(0.16oZ)/m(ft)
NOTE: The nominal capacity and energy efficiency are tested
meter piping on specification or nameplate).
NOTE: The number of bends is up to the length of the max
Page 25
9.52(3/8")
(Total pipe length -
standard pipe length)
x30g(0.32oZ)/m(ft)
based on pipe length of 5 meter (please refer refrigerant charge amount of 5
Extend pipe length will reduce the capacity and energy efficiency
height drop. Usually for each 10m need a bend.
12.7(1/2")
(Total pipe length -
standard pipe length)
x65g(0.69oZ)/m(ft)
of the unit.