R
Fan command value
Enable fan command
value
K NX
R
Fan operation
Fan stage 1-2-3
Fan output
3-speed fan control
with modulating
heating / cooling
control
Note:
3-speed fan control
with ON/OFF heating /
cooling control
Look-up table with
ON/OFF control
40 / 80
Siemens
Building Technologies
3.8

Fan control

The fan operates in automatic mode or at the selected speed with manual mode.
In automatic mode, the fan speed depends on the setpoint and the current room
temperature. When the room temperature reaches the setpoint, the control valve
closes and the fan switches off or stays at fan speed 1 (parameter P60; factory
setting: 0 = fan speed 1 in dead zone).
The fan speed and mode can be changed via bus.
For this purpose, the fan command value needs to be enabled.
The fan speed and mode can be monitored via bus.
The individual switching points for ON of each fan stage can be adjusted via control
parameters P55...P57. The fan speed switch off point is 20% below the switch on
point. The diagrams below show fan speed control for modulating PI control.
Q
Q3
Q2
Q1
100
0
w
x
Y
[%]
XpH
dz
H
The diagram only shows the PI thermostat's proportional part.
On applications with 2-position control:
1) The switching point for low fan speed (Q1) is synchronized to the heating /
cooling output. Parameter "Switching point fan speed low" P57 is not relevant.
2) The maximum switching range of the fan (XpH
switching differential (SDH/SDC) via a look-up table.
Y
x
1
0
SDH
Q
Q3
Q2
Q1
w
XpH
Fan
SDH/SDC
[K]
0.5
XpH
/XpC
[K]
2
Fan
Fan
RDF301, RDF301.50 Basic documentation
Functions
0
100
XpC
Y
[%]
C
dz
w
T[°C]
SDC
Cool
T[°C]
XpC
Fan
1.0
1.5
2.0
3
4
5
w
Room temperature setpoint
Q
Fan speed
Y
Control demand "Heating"
H
Y
Control demand "Cooling"
C
XpH
Proportional band "Heating"
XpC
Proportional band "Cooling"
X
Dead zone
dz
/ XpC
) is defined by the
Fan
Fan
T[°C]
Room temperature
w
Room temperature setpoint
Q
Fan speed
Y
Control command "Valve"
SDH
Switching differential "Heating"
SDC
Switching differential "Cooling"
X
Dead zone
dz
XpH
Switching range for fan "Heating"
Fan
XpC
Switching range for fan "Cooling"
Fan
2.5
3.0
3.5
4.0
6
7
8
9
>4.5
10
CE1P3171en