(dec)
0013-001F 0019-
RESERVED
0031
BURNER CONTROL
STATUS
0020
0032
Burner control status
0021
0033
Burner control state
0022
0034
Lockout code
0023
0035
Alarm reason
0024
0036
Annunciator first out
0025
0037
Annunciator Hold
0026
0038
Sequence time
0027
0039
Delay time
0028
0040
Hold code
0029
0041
Burner control flags
002A
0042
Remote Stat
750-265
Table 33. CB Falcon Global Modbus Register Map. (Continued)
Read/
Parameter
Write
R
R
R
R
R
R
R
R
R
R
R/W
Format
U16
0=Disabled
1=Locked out
2=Standby Hold
3=Unconfigured safety data
4-15=Reserved
16=Normal Standby
17=Preparing
18=Firing
19=Postpurge
U16
Burner control sequence (I/O) state.
Model type determined by register 176.
U16
0=No lockout,
1-4096 (see Table 37)
U16
0=None
1=Lockout (see Lockout code, register 34)
2=Other (alert)
U16
Source for annunciator first out:
0=None or undetermined
1=ILK
2=PII
11=Annunciator 1
12=Annunciator 2
13=Annunciator 3
14=Annunciator 4
15=Annunciator 5
16=Annunciator 6
17=Annunciator 7
18=Annunciator 8
U16
Source for burner control hold condition (see Hold
code):
0=None or undetermined
1=ILK
2=PII
3=LCI
11=Annunciator 1
12=Annunciator 2
13=Annunciator 3
14=Annunciator 4
15=Annunciator 5
16=Annunciator 6
17=Annunciator 7
18=Annunciator 8
U16
Running time for timed burner control operation
(seconds)
U16
Running delay time (seconds). Applicable when burner
control in delayed or hold state.
U16
Source/reason for burner hold (same codes as lockout,
see Table 37)
U16
Bit map:
15-1=Reserved (always 0)
0= Flame detected
U16
0=No remote STAT demand,
1=remote STAT demand indicated