Electrical Installation - Siemens SINAMICS G120P Operating Instructions Manual

Filter for pm330 power module
Hide thumbs Also See for SINAMICS G120P:
Table of Contents

Advertisement

Electrical installation

Important safety precautions
Dangerous electrical voltage
The devices are operated with high voltages.
All connection work must be carried out in a no-voltage condition!
All work on the device must be carried out by trained personnel only.
Death, serious injury, or substantial material damage can result if these warning notices are
not observed.
Work on an open device must be carried out with extreme caution because external supply
voltages may be present. The power and control terminals may be live even when the
motor is not running.
Dangerously high voltage levels are still present in the cabinet up to 5 minutes after it has
been disconnected due to the DC link capacitors on the Power Module. For this reason, the
unit should not be opened until a reasonable period of time has elapsed.
The operator is responsible for ensuring that the du/dt filter compact plus Voltage Peak
Limiter and other components are installed and connected in accordance with the
recognized technical rules in the country of installation and applicable regional guidelines.
Special attention should be paid to cable dimensioning, fuses, grounding, shutdown,
disconnection, and overcurrent protection.
If a protective device trips in a branch circuit, a fault current may have been interrupted. To
reduce the risk of fire or an electric shock, the current-conducting parts and other
components in the cabinet unit should be inspected and damaged parts replaced. When a
protective device trips, the cause of the trip must be identified and rectified.
dV/dt filter compact plus Voltage Peak Limiter
Operating Instructions, 11/2013, A5E32847614B AA
WARNING
4
17

Advertisement

Table of Contents
loading

Table of Contents