13.10.2 Sequence for automatic test run

Time Test Run
100 h
the last stop for 20 seconds with the in parameter 13.10.3 set speed.
Deactivating test run: Set 0 hours, by using
Repeating the test run: Select test run and set the desired hours using the key
Press
on the controller to change to

13.10.3 Test Run: Frequency

Test Frequency
30.0 Hz
Press
on the controller to change to

13.10.4 Test Run: Boost

BOOST Test Run
10.0 %.
To leave the submenu press the

13.11 Submenu Error

Submenu

13.11.1 Conveyor Limit

Conveyor Limit
0.0 bar
"0.0 bar" means disabled conveyor limit.
An adjusted value >0 has to be reached till the programmed "ERROR DELAY"-time.
Doesn't this value be reached the failure "ERROR WATER" will be indicated and the
pump stops.
Press
on the controller to change to

13.11.2 Error Delay

Adjustable between 1...100 hours.
The test run starts the pump at the set time after
Frequency for manual and automatic test run.
Can be set from 0 Hz up to 70 Hz.
Start voltage in % of rated voltage in order to ensure
that the motor starts safely. Adjustable between 0%
and 25%
To enter this menu you have to press the
Error
leave the menu, press the
Disabled or adjustable between 0 and 10 bar of the
analogue input signal range.