The following procedure provides the steps for calibrating the output signal for a Transmitter in the
analog mode. The procedure is similar for a Transmitter in the DE mode, but the MC Toolkit is
required to read the output in percent in place of current or voltage.
for the analog output calibration process.
1. Verify the integrity of the electrical components in the output current loop.
2. Connect the MC Toolkit as indicated, and establish communication with the Transmitter. For
these procedures, values of components in the current loop are not critical, if they support
reliable communication between the Transmitter and the MC Toolkit.
3. Start the MC Tookit application, and establish communication with the Transmitter.
4. In the Output Calibration box, click the Loop Test button to display the LOOP TEST box.
5. Click the desired constant-level Output: 0 %, 100 %, or Other (any of 0 % - 100 %).
6. Click the Set button. You will be prompted to confirm that you want to put the Transmitter in
output mode.
Page 56
Figure 10 – Analog Output Calibration Test Setup
ST 700 Series HART/DE Option User's Manual
Figure 10
illustrates the test setup
Revision 4.0