9.2.4 TV Tracking Diagnostics

Max TV Limit
Parameter
Max TV Value
Parameter
Time Above
Parameter
Upper Stress
Limit
Time Since
Method
Last TV Up

9.2.5 ET Tracking Diagnostics

Max ET Limit
Parameter
ET Upper
Limit for
Stress
Condition
Max ET Value
Parameter
Time Above
Parameter
Upper Stress
Limit
Revision 4.0
Table 20 – TV Tracking Diagnostics
Description
Set-up
Description
Set-up
NVM
Description
Set-up
NVM
Description
Set-up
NVM
Table 21 – Maximum ET Diagnostics
Description
Set-up
Description
Example
Set-up
Description
Set-up
NVM
Description
Set-up
NVM
ST 700 Series HART/DE Option User's Manual
Static Pressure upper operating limit
specification.
Units are always PSI (pounds per square
inch).
None.
Highest SP ever experienced by the device.
Units are always PSI (pounds per square
inch).
None.
Backup once each 8 hour period
Accumulation of minutes that device's SP
has been above the value of "SP Upper
Stress Limit".
None.
Backup once each 8 hour period
Time that has passed since the last time
device's SP has passed above the value of
"SP Upper Stress Limit" (in days, hours, and
minutes).
None.
Backup once each 8 hour period
Electronics Temperature (ET) upper
operating limit from specification.
Units are same degree units as has been
selected for SV (Secondary Variable).
None.
Actual limit used in "Time Above Limit" and
"Time Since Last Event". Value is equal to
"Max ET Limit" less 10% of limits range.
Electronics Temperature range is -40F to
185F for a total of 225F.
ET Upper Stress Limit= 185F - 10% of
225F = 162.5F.
None: calculation is automatic.
Highest Electronics Temperature ever
experienced by the device.
Units are same degree units as has been
selected for SV (Secondary Variable).
None.
Update every 8 hour.
Accumulation of minutes that device's
Electronics Temperature has been above
the value of "ET Upper Stress Limit".
None.
Backup once each 8 hour period