ATTACHING TO OTHER CCN MODULES — If
chiller ICVC has been connected to a CCN Network or other
PIC- controlled chillers through CCN wiring, the ICVC can be
used to view or change parameters on the other controllers.
Other PIC III chillers can be viewed and set points changed (if
the other unit is in CCN control), if desired, from this particular
ICVC module.
If the module number is not valid, the "COMMUNICA-
TION FAILURE" message will show and a new address num-
ber must be entered or the wiring checked. If the module is
communicating properly, the "UPLOAD IN PROGRESS"
message will flash and the new module can now be viewed.
Whenever there is a question regarding which module on
the ICVC is currently being shown, check the device name
descriptor on the upper left hand corner of the ICVC screen.
See Fig. 35.
When the CCN device has been viewed, the ATTACH TO
NETWORK DEVICE table should be used to attach to the PIC
that is on the chiller. Move to the ATTACH TO NETWORK
DEVICE table (LOCAL should be highlighted) and press the
softkey to upload the LOCAL device. The ICVC
ATTACH
for the 23XRV chiller will be uploaded and default screen will
display.
NOTE: The ICVC will not automatically reattach to the local
module on the chiller. Press the
the LOCAL device and view the local chiller operation.
Service Operation —
screens available for the SERVICE function is shown in
Fig. 28.
TO ACCESS THE SERVICE SCREENS — When
SERVICE screens are accessed, a password must be entered.
1. From the main MENU screen, press the
softkey. The softkeys now correspond to the numerals
1, 2, 3, 4.
2. Press the four digits of the password, one at a time. An
asterisk (*) appears as each digit is entered.
NOTE: The initial factory-set password is 1-1-1-1.
If the password is incorrect, an error message is
displayed.
If this occurs, return to Step 1 and try to access the
SERVICE screens again. If the password is correct, the
softkey labels change to:
NOTE: The SERVICE screen password can be changed by
entering the ICVC CONFIGURATION screen under
SERVICE menu. The password is located at the bottom of the
menu. Contact Carrier Service to override the ICVC password
if it is lost.
softkey to attach to
ATTACH
An overview of the tables and
SERVICE
the
The ICVC screen displays the following list of available
SERVICE screens:
• Alarm History
• Alert History
• Control Test
• Control Algorithm Status
• Equipment Configuration
• VFD Config Data
• Equipment Service
• Time and Date
• Attach to Network Device
• Log Out of Device
• ICVC Configuration
See Fig. 28 for additional screens and tables available from
the SERVICE screens listed above. Use the
return to the main MENU screen.
NOTE: To prevent unauthorized persons from accessing the
ICVC service screens, the ICVC automatically signs off and
password-protects itself if a key has not been pressed for
15 minutes. The sequence is as follows. Fifteen minutes after
the last key is pressed, the default screen displays, the ICVC
screen light goes out (analogous to a screen saver), and the
ICVC logs out of the password-protected SERVICE menu.
The STATUS, SCHEDULE, and SETPOINT screens can be
accessed without the password by pressing the appropriate
softkey.
TO LOG OUT OF DEVICE — To access this screen and log
out of a network device, from the default ICVC screen, press
the
and
MENU
and, from the SERVICE menu, highlight LOG OUT OF
NETWORK DEVICE and press the
the
ICVC default screen will now be displayed.
HOLIDAY SCHEDULING (Fig. 36) — The time schedules
may be configured for special operation during a holiday
period. When modifying a time period, the "H" in the far right
column of the OCCPC01S, OCCPC02S or OCCPC03S time
schedule screen signifies that the period is applicable to a
holiday. (See Fig. 29.)
The TIME BROADCAST ENABLE function must be
activated for the holidays configured on the HOLIDAYS
screen to work properly. Access the BRODEF screen from the
EQUIPMENT CONFIGURATION table, highlight TIME
BROADCAST ENABLE and select ENABLE to activate func-
tion. Note that when the chiller is connected to a CCN network,
only one chiller or CCN device can be configured as the broad-
cast device. The controller that is configured as the broadcaster
is the device responsible for transmitting holiday, time, and
daylight-savings dates throughout the network.
To access the BRODEF screen, see the SERVICE menu
structure, Fig. 28.
To view or change the holiday periods for up to 18 different
holidays, perform the following operation:
1. At the Main Menu screen, press
the Service menu.
2. If not logged on, follow the instructions for ATTACH
TO NETWORK DEVICE CONTROL or To Log Out
of Device. Once logged on, press
EQUIPMENT CONFIGURATION is highlighted.
3. Once EQUIPMENT CONFIGURATION is high-
lighted, press
4. Press
NEXT
the Holiday Definition table.
5. Press
SELECT
screen.This screen lists 18 holiday tables.
59
EXIT
softkeys. Enter the password
SERVICE
SELECT
SERVICE
NEXT
to access.
SELECT
until HOLIDAYS is highlighted. This is
to enter the Data Table Select
softkey to
softkey. The
to access
until