Carrier AquaEdge 23XRV Start-Up, Operation And Maintenance Instructions Manual page 167

High-efficiency variable speed screw chiller with greenspeed intelligence and pic iii controls 50/60 hz hfc-134a
Table of Contents

Advertisement

INITIAL START:
Check Position of all Valves:
Isolation Valves (See Fig. 2-4, 41-43, and 45)
VALVE
Discharge
Cooler Inlet
Hot Gas Bypass
Vaporizer Condenser Gas
Oil Pump
Oil Filter
Oil Pressure Regulator
Filter/Drier
Filter/Drier
VFD Refrigerant Cooling Inlet
VFD Refrigerant Cooling Drain
Relief Valve Three-Way Valves
Cooler (if installed)
Condenser
Service Valves
Cooler Refrigerant Charging Valve
Cooler Refrigerant Pumpout Valve
Condenser Refrigerant Charging Valve
Condenser Refrigerant Pumpout Valve
Oil Sump Charging/Drain Valve
Start Liquid Pumps and Establish Liquid Flow
Oil Level OK and Oil Temperature OK
Restart Compressor, Bring Up To Speed. Shut Down. Any Abnormal Coastdown Noise?
*If yes, determine cause.
START MACHINE AND OPERATE. COMPLETE THE FOLLOWING:
A: Trim charge and record under Charge Refrigerant Into Chiller section on page 79.
B: Inspect refrigerant cooling lines for condensation (Q,R compressors only). See page 71.
B: Complete any remaining control calibration and record under Controls section (pages 18-60).
C: Take at least two sets of operational log readings and record.
D: After machine has been successfully run and set up, shut down and mark shutdown oil levels.
E: Give operating instructions to owner's operating personnel.
F: Call your Carrier factory representative to report chiller start-up.
G: Rockwell/Allen Bradley VFD: Register drive start-up at www.automation.rockwell.com/warp.
Eaton VFD: Complete Eaton Warranty Registration Form TD08H28TE and send to:
VFDAftermarketEG@eaton.com
NOTE: To extend drive warranty, registration should be performed by a Rockwell or Eaton Certified Technician as
applicable.
H: Return a copy of this completed checklist to the local Carrier Service office.
SIGNATURES:
CARRIER
TECHNICIAN
DATE
LOCATION
Under Muffler
Next to economizer or under cooler
Between cooler and condenser
Between cooler and condenser
Next to oil pump inlet
Downstream of oil filter
Under oil sump next to oil pressure regulator
Next to condenser float chamber
Under condenser near filter/drier
Under compressor discharge
Between cooler and condenser
Fully Front Seated or Fully Back Seated
Fully Front Seated or Fully Back Seated
On cooler relief valve tree
Under cooler
On condenser relief valve tree
On condenser float valve chamber
Under oil sump
Oil Pressure
CUSTOMER
REPRESENTATIVE
DATE
CL-3
Hours Given:
OPEN
________
________
________
________
________
________
________
________
________
________
________
________
________
CLOSED
________
________
________
________
________
Yes*
No
Hours