Carrier AquaEdge 23XRV Start-Up, Operation And Maintenance Instructions Manual page 38

High-efficiency variable speed screw chiller with greenspeed intelligence and pic iii controls 50/60 hz hfc-134a
Table of Contents

Advertisement

To access this display from the ICVC default screen:
1. Press
MENU
.
2. Press
SERVICE
.
3. Scroll down to highlight
CONTROL ALGORITHM STATUS
4. Press
.
SELECT
5. Scroll down to highlight
VFD_HIST
DESCRIPTION
VFD FAULT HISTORY
Values At Last Fault:
Line Current Phase 1 (R)
Line Current Phase 2 (S)
Line Current Phase 3 (T)
Load Current Phase 1 (U)
Load Current Phase 2 (V)
Load Current Phase 3 (W)
Line Voltage Phase 1 (RS)
Line Voltage Phase 2 (ST)
Line Voltage Phase 3 (TR)
Ground Fault Current
Line Frequency
Line Power Factor
Line Current Imbalance
Line Voltage Imbalance
Motor Power Factor
Motor Current Imbalance
Motor Overload
Line Active Current
Line Reactive Current
Line Active Voltage
Line Reactive Voltage
DC Bus Voltage
DC Bus Voltage Reference
Flux Current
Torque Current
Inverter Temperature
Rectifier Temperature
VFD Dewpoint
VFD Enclosure Temp
VFD Cold Plate Temp
Actual VFD Speed
Comp Motor RPM
Comp Motor Frequency
Chiller Fault State
VFD Fault Code
NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation;
forcing shall not be supported on maintenance screens.
To access this display from the ICVC default screen:
1. Press
MENU
.
2. Press
SERVICE
.
3. Scroll down to highlight
CONTROL ALGORITHM STATUS
4. Press
.
SELECT
LOADSHED
5. Scroll down to highlight
DESCRIPTION
LOADSHED FUNCTION
Redline
Loadshed
Loadshed Timer
NOTE: All variables with CAPITAL LETTER point names are avail-
able for CCN read operation; forcing shall not be supported on main-
tenance screens.
Table 3 — ICVC Display Data (cont)
EXAMPLE 15 — VFD_HIST DISPLAY SCREEN
.
.
STATUS
0 to 99999
0 to 99999
0 to 99999
0 to 99999
0 to 99999
0 to 99999
0 to 99999
0 to 99999
0 to 99999
0 to 999
0 to 99
0 to 2.0
0 to 100
0 to 100
0 to 2.0
0 to 100
0 to 100
0 to 99999
0 to 99999
0 to 99999
0 to 99999
0 to 99999
0 to 99999
0 to 99999
0 to 99999
0 to 300
0 to 300
0.0 to 300.0
0 to 300
0 to 300
0 to 100
0 to 300000
0 to 10000
200 to 272
200 to 272
EXAMPLE 16 — LOADSHED DISPLAY SCREEN
.
.
STATUS
0/1
0/1
0 to 480
UNITS
AMPS
AMPS
AMPS
AMPS
AMPS
AMPS
VOLTS
VOLTS
VOLTS
AMPS
Hz
%
%
%
%
AMPS
AMPS
VOLTS
VOLTS
VOLTS
VOLTS
AMPS
AMPS
°F (°C)
°F (°C)
°F (°C)
°F (°C)
°F (°C)
%
rpm
Hz
UNITS
NO/YES
NO/YES
38
POINT
LNAMPS1H
LNAMPS2H
LNAMPS3H
LDAMPS1H
LDAMPS2H
LDAMPS3H
LNVOLT1H
LNVOLT2H
LNVOLT3H
GF_AMPSH
LINEFRQH
LINE_PFH
LN_IMBIH
LN_IMBVH
MOTORPFH
MT_IMBIH
MOTOROVH
AMPSACTH
AMPS_REH
VOLTACTH
VOLT_REH
BUSVOLTH
BUS_REFH
FLUXAMPH
TORQAMPH
INVTEMPH
RECTEMPH
VFDDEWPT
VFDENCLH
CP_TEMPH
VFD_ACTH
CPR_RPMH
VFDFREQH
VFDSTATH
VFD_FLTH
POINT
REDLINE
LOADSHED
LOADTIME