Chiller Shipped With Holding Charge - Carrier AquaEdge 23XRV Start-Up, Operation And Maintenance Instructions Manual

High-efficiency variable speed screw chiller with greenspeed intelligence and pic iii controls 50/60 hz hfc-134a
Table of Contents

Advertisement

COOLER
FRAME SIZE
LENGTH
FT (M)
12
(3.6)
3
14
(4.3)
12
(3.6)
4
14
(4.3)
12
(3.6)
5
14
(4.3)
FRAME SIZE
A1
A2
A3
A4
A5
A6
B1
B2
B3
B4
B5
B6
CHILLER SHIPPED WITH HOLDING CHARGE — Use the
CONTROL TEST TERMINATE LOCKOUT function to
monitor conditions and start the pumps.
If the chiller has been shipped with a holding charge, the
refrigerant is added through the refrigerant charging valve
(Fig. 40-43, valves 1a and 1b) or to the pumpout charging con-
nection. First evacuate the nitrogen holding charge from the
chiller vessels. Charge the refrigerant as a gas until the system
pressure exceeds 35 psig (141 kPa) for HFC-134a. After the
chiller is beyond this pressure the refrigerant should be charged
as a liquid until all the recommended refrigerant charge has
been added.
TRIMMING REFRIGERANT CHARGE — T h e 2 3 X R V
chiller is shipped with the correct charge for the design duty of
the chiller. The LTD (leaving temperature difference) between
the EVAP REFRIG LIQUID TEMP and LEAVING CHILLED
LIQUID can be checked against the design conditions to con-
firm that the charge is correct. In the case where leaks have
been found and corrected and the LTD is greater than about
4° F (2.2° C) above design, add refrigerant until the full load
design LTD is approached. (A high cooler LTD can also be
caused by dirty tubes, water box division plate bypass, a par-
tially closed liquid isolation valve, or the float valve.)
Table 16 — Refrigerant Charges, Frame Sizes 3-5
COOLER
CODE
lb (± 25 lb)
30
31
32
35
36
37
40
41
42
45
46
47
50
51
52
55
56
57
Table 17 — Refrigerant Charges, Frame Sizes A,B
COOLER LENGTH
FT (M)
lb (± 25 lb)
12
(3.6)
14
(4.3)
CHARGE AMOUNT (R-134a)
WITH ECONOMIZER
kg (± 11 kg)
800
363
800
363
800
363
910
413
910
413
910
413
900
408
900
408
900
408
1015
460
1015
460
1015
460
1250
567
1250
567
1250
567
1430
649
1430
649
1430
649
CHARGE AMOUNT (R-134a)
WITH ECONOMIZER
kg (± 11 kg)
840
381
860
390
880
399
900
408
930
422
960
435
950
431
970
440
1000
454
1020
463
1060
481
1090
494
Trimming the charge can best be accomplished when the
design load is available. The calibration of the EVAP REFRIG
LIQUID TEMP and LEAVING CHILLED LIQUID tempera-
ture sensors should be confirmed prior to checking for proper
cooler LTD. Compare the difference between EVAP REFRIG
LIQUID TEMP and LEAVING CHILLED LIQUID tempera-
tures to the chiller design conditions. Add or remove refriger-
ant, if necessary, to bring the cooler leaving temperature
difference to design conditions or within minimum differential.
Check for low load oil recovery after making adjustments to
the refrigerant charge. The bubbling mixture of refrigerant and
oil mixture should be visible through the vaporizer sight glass
at low load when the oil reclaim valve is open. If a bubbling
mixture is not observed when the oil reclaim valve is open, add
refrigerant.
The preferred location at which refrigerant should be added
directly into the chiller is through the service valves on top of
the cooler condenser. if these valves are not accessible due to
presence of an attached pumpdown unit which does not have a
storage tank, slowly add charge through the valve connected to
the side of the condenser drain float sump. Adding charge
through the cooler refrigerant pumpout valve at the base of the
cooler (off the liquid line) may force debris into the condenser
float valve and is not recommended.
81
WITHOUT ECONOMIZER
lb (± 25 lb)
kg (± 11 kg)
650
295
650
295
650
295
760
345
760
345
760
345
750
340
750
340
750
340
865
392
865
392
865
392
1100
499
1100
499
1100
499
1280
581
1280
581
1280
581
WITHOUT ECONOMIZER
lb (± 25 lb)
kg (± 11 kg)
820
372
840
381
860
390
880
399
910
413
940
426
930
422
950
431
980
445
1000
454
1040
472
1070
485

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents