Cooling And Degrees Of Protection - ABB ACS850 Hardware Manual

Acs850-04 drive modules (1.1 to 45 kw)
Hide thumbs Also See for ACS850:
Table of Contents

Advertisement

29
Note: EMC filters of type JFI-x1 mounted directly above the drive module do not
increase the free space requirements. (For EMC filters of type JFI-0x, see the
dimension drawing of the filters on page 115.)
200 mm [7.9"]
300 mm [12"]
The temperature of the cooling air entering the unit must not exceed the maximum
allowed ambient temperature (see
Ambient conditions
in the chapter
Technical
data). Consider this when installing heat-generating components (such as other
drives, mains chokes and braking resistors) nearby.

Cooling and degrees of protection

The cabinet must have enough free space for the components to ensure sufficient
cooling. Observe the minimum clearances given for each component.
The air inlets and outlets must be equipped with gratings that
• guide the air flow
• protect against contact
• prevent water splashes from entering the cabinet.
The drawing below shows two typical cabinet cooling solutions. The air inlet is at the
bottom of the cabinet, while the outlet is at the top, either on the upper part of the
door or on the roof.
Planning the cabinet assembly