Figure 3-8 Typical Motor Rating Plate Example - Siemens MICROMASTER 430 Operating Instructions Manual

3ac-frequency inverter
Hide thumbs Also See for MICROMASTER 430:
Table of Contents

Advertisement

Issue 10/06
Motor data for parameterization

Figure 3-8 Typical Motor Rating Plate Example

NOTICE
P0308 & P0309 are only visible if P0003 ≥ 2. Only one of the parameters is
shown depending on the settings of P0100.
P0307 indicates kW or HP depending upon the setting of P0100. For detailed
information, please see the Parameter List.
Changing motor parameters is not possible unless P0010=1.
Ensure that the inverter is configured correctly to the motor.
Observe the motor's star/delta connection arrangement!
3.2.4
Reset to Factory default
To reset all parameters to the factory default settings; the following parameters
should be set as follows (BOP-2 or Communication Option needed):
1. Set P0010=30.
2. Set P0970=1.
NOTE
The reset process can take up to 3 minutes to complete.
MICROMASTER 430
Operating Instructions
6SE6400-5AE00-0BP0
(The details given on the rating plate are only examples)
http://nicontrols.com
3 Commissioning
57

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents