4.3.5
Compound braking
Compound braking is possible with OFF1 and OFF3. In the case of compound
braking, a DC component is superimposed on the alternating current.
Set braking current :
4.4

Control modes (P1300)

MICROMASTER 430 has a number of different control modes based on U/f-
control. The individual modes have been listed below, additional settings are listed
in the parameter list and the function plans contained therein.
Linear U/f control
Can be used for variable and constant torque applications e.g. transport
systems and positive displacement pumps.
Linear U/f control with flux current control (FCC)
This type of control can be used to improve the performance and dynamic
behaviour of the motor.
Parabolic U/f control
This type of control can be used for variable torque loads e.g. fan and pumps.
Multiple point U/f control
Please refer to the MICROMASTER 430 parameter list for more information on
this operating mode.
U/f control for textile applications
There is no slip compensation gain or resonance dampening. The Imax
controller refers to voltage instead of frequency.
U/f control with FCC for textile applications
A combination of P1300 = 1 and P1300 = 5.
U/f control with independent voltage set point
Using the P1330, the voltage set point can be given independently from the
starting frequency of the ramp function generator (HLG).
MICROMASTER 430
Operating Instructions
6SE6400-5AE00-0BP0
see P1236
http://nicontrols.com
4 MICROMASTER 430 functions
P1300 = 0
P1300 = 1
P1300 = 2
P1300 = 3
P1300 = 5
P1300 = 6
P1300 = 19
65