3. COMMISSIONING
Motor data for parameterization

Figure 3-5 Typical Motor Rating Plate Example

Note
P0308 & P0309 are only visible if P0003 ≥ 2. Only one of the parameters are shown
depending on the settings of P0100.
Changing motor parameters is not possible unless P0010=3.
Ensure that the inverter is configured correctly to the motor, i.e. in the above example
delta terminal connection is for 230 V.
External motor thermal overload protection
Motor
PTC
1 kΩ
Figure 3-6
Note:
To enable the trip function, set parameter P0701, P0702 or P0703 = 29.
MICROMASTER 420 Operating Instructions
6SE6400-5AA00-0BP0
P0308 P0310
P0304
3_Mot
IEC 56
IM B3
50 Hz
230-400V
0.61 0.35 A
0.12kW
Cos
0.81
j
2800 / min
95.75%
P0309
P0305 P0311 P0307
8
Inverter Control
5, 6
Terminals
or 7
9
Motor Overload PTC Connection
12.022
Nr. ED510 3053
I.CI.F
IP54
Rot KL 16
60 Hz
440V Y
0.34A
0.14 kW
Cos
0.81
j
3310 /min
S.F. -- 1.15
When operated below rated speed, the
cooling effect of fans fitted to the motor
shaft is reduced. Consequentially, most
motors require de-rating for continuous
operation at low frequencies. To ensure
that the motors are protected against
overheating under these conditions, a
PTC temperature sensor must be fitted to
the motor and connected to the inverter
control terminals as shown in Figure 3-6.
International English
33