2 Installation
2.3

Mechanical installation

WARNING
To ensure the safe operation of the equipment, it must be installed and
commissioned by qualified personnel in full compliance with the warnings laid
down in these operating instructions.
Take particular note of the general and regional installation and safety
regulations regarding work on dangerous voltage installations (e.g. EN 50178),
as well as the relevant regulations regarding the correct use of tools and
personal protective equipment (PPE).
The mains input, DC and motor terminals, can carry dangerous voltages even if
the inverter is inoperative; wait 5 minutes to allow the unit to discharge after
switching off before carrying out any installation work.
The inverters can be mounted without any clearance at either side. When
mounting inverters one above the other, the specified environmental conditions
must not be exceeded. Independent of this, these minimum distances must be
observed.
♦ Frame Size C
♦ Frame Size D, E
♦ Frame Size F
♦ Frame Size FX, GX
If the front cover (Frame Sizes FX and GX) has been removed, the fan impeller
is exposed. There is danger of injury when the fan is running.
IP20 protection is only against direct contact, always use these products within
a protective cabinet.
Removing from transport pallet (only for framesizes FX and GX)
During transport, the inverter is fastened on the transport pallet with the aid of two
iron brackets.
WARNING
Note that the center of gravity of the inverter is not in the middle of the unit. When
lifting the pallet, the unit can therefore suddenly change position and swing to the
side.
1. Fasten the hoisting crane cable to the hoisting eyes on the inverter (2 eyes
(see Figure 2-9 for frame size FX Figure 2-10 for frame size GX).
2. Remove the two retaining bolts at the top of the front cover.
3. Unscrew the bolts in the iron brackets on the transport pallet and lift the
inverter off the pallet.
4. Once installation has been completed and the inverter connected, fasten the
two retaining bolts for the front cover at the bottom side of the door.
24
above and below 100 mm
above and below 300 mm
above and below 350 mm
above 250 mm
below 150 mm
in front 40 mm (FX), 50 mm (GX)