3 Commissioning
3.2.1
Commissioning with the SDP
In addition, the following conditions must be met:
Linear V/f motor speed controlled by an analog potentiometer.
Maximum speed 1500 rpm at 50 Hz (1800 rpm at 60 Hz); can be controlled by
a potentiometer via the analog inputs of the inverter.
Ramp-up time = 10 s
Ramp-down time = 30 s
Settings for more complex applications can be found in the parameter list and in
Section 3.2.2 "Commission Overview with BOP-2".
Table 3-1
Digital Input 1
Digital Input 2 *
Digital Input 3
Digital Input 4
Digital Input 5
Digital Input 6
Digital Input 7
Digital Input 8
* The standard setting for the change of rotation direction is as inhibited.
(Parameter 1110)
48
The SDP has two LEDs on the front which display the
current operating status of the inverter (see Section 6.1).
When the SDP is used, the presettings of the inverter
must be compatible with the following motor data:
Rated motor power
Motor voltage
Rated motor current
Rated motor frequency
(A conventional Siemens motor is recommended)
Default settings for operation using the SDP
Terminals
Parameter
5
P0701 = '1'
6
P0702 = '12'
7
P0703 = '9'
8
P0704 = '15'
16
P0705 = '15'
17
P0706 = '15'
Via AIN1
P0707 = '0'
Via AIN2
P0708 = '0'
http://nicontrols.com
Default Operation
ON right
Reverse
Fault Acknowledge
Fixed Frequency
Fixed Frequency
Fixed Frequency
Inactive
Inactive
MICROMASTER 430
Operating Instructions
6SE6400-5AE00-0BP0
Issue 10/06