EntelliGuard®TU Trip Unit
Appendix 1 – Communications Parameters

APPENDIX 1: COMMUNICATIONS PARAMETERS

Table 22: Communications Parameters – Modbus Function 2
Register
Variable
5
Relay 1 Status
6
Relay 2 Status
7
Relay 3 Status
8
Relay 4 Status
9
Input 1 Status
10
Input 2 Status
11
Input 3 Status
12
Input 4 Status
27
Breaker position
34
Cassette Indication
35
Draw Out
44
Remote Close
61
GF Sum Alarm Status
62
GF CT Alarm Status
Table 23: Communications Parameters – Modbus Function 3
Register
2
GF Protection Sun Enable
5
No. of Poles
6
Protective Relays Enable
7
Full Metering Enable
8
Neutral Position
10
Long Time Protection Enable
18
Agency Standard
20
GTU Model Type
22
Current Sensor Rating
24
Ground Fault Sum Alarm Enable
25
Ground Fault CT Alarm Enable
31
Current Alarm Enable
35
ZSI Enable
79
ST Switchable
81
Instantaneous
82
LT Switchable
84
Fuse Protection
86
GF Protection CT Enable
95
GF CT Switchable
98
Breaker Serial Number – Low 16 bit
99
Breaker Serial Number – High 16 bits
107
Reduce Instantaneous
206
Neutral Pole Rating
207
ZSI Combination
26
Courtesy of NationalSwitchgear.com
0 – OFF, 1 – ON
0 – OFF, 1 – ON
0 – OFF, 1 – ON
0 – OFF, 1 – ON
0 – OFF, 1 – ON
0 – OFF, 1 – ON
0 – OFF, 1 – ON
0 – OFF, 1 – ON
0 – OFF, 1 – ON
0 – OFF, 1 – ON
0 – OFF, 1 – ON
0 – OFF, 1 – ON
0 – Normal, 1 – Alarm
0 – Normal, 1 – Alarm
Variable
0–Disable, 1–Enable
0–3 Pole, 1–4 Pole
0–Disable, 1–Enable
0–Disable, 1–Enable
0–Disable, 1–Enable
0–Disable, 1–Enable
0–UL, 1–IEC, 2–ANSI
0– GTU C, 1–GTU D, 4–GTU ACB
1–150 A
2–200 A
3–225 A
4–400 A
5–600 A
6–800 A
7–1000 A
0–Disable, 1–Enable
0–Disable, 1–Enable
0–Disable, 1–Enable
0–Disable, 1–GT-ST (Z), 2–GR-ST-Inst (T)
0–Disable, 1–Enable
0–Disable, 1–15X Switchable, 2–15X Non-Switchable
3–30X Switchable, 4–30X Non-Switchable
0–Disable, 1–Enable
0–Disable, 1–Enable
0–Disable, 1–Enable
0–Disable, 1–Enable
-
-
0–Disable, 1–Enable
0–50%, 1–63%, 2–100%
0
1–GF
Value
Value
8–1200 A
15–5000 A
9–1600 A
16–6000 A
10–2000 A
17–630 A
11–2500 A
18–1250 A
12–3000 A
19–6400 A
13–3200 A
20–Universal spare
14–4000 A
4–Instantaneous
5–GF and Inst
© 2008 General Electric All Rights Reserved
09/25/08
Read/Write
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read/Write
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read/Write
Read/Write