Siemens SIMATIC S7-400 Reference Manual page 84

Automation system module data
Hide thumbs Also See for SIMATIC S7-400:
Table of Contents

Advertisement

Digital modules
4.1 Module overview
Table 4-2
Digital output modules: overview of features
Features
SM 422;
DO 16xDC
24 V / 2 A
(-1BH1x)
Number of
16 DO; isola‐
outputs
ted in groups
of 8
Output cur‐
2 A
rent
Nominal
24 VDC
load voltage
Configura‐
No
ble
diagnostics
Diagnostic
No
interrupt
Substitu‐
No
tion value
output
Special fea‐
For high cur‐
tures
rents
Table 4-3
Relay output module: overview of features
Features
Number of outputs
Load voltage
Special features
84
SM 422;
SM 422;
DO 16xDC
DO 32xDC
20-125 V/ 1.5
24 V / 0.5 A
A
(-5EH10)
(-1BL00)
16 DO; isola‐
32 DO; isola‐
ted and re‐
ted in groups
verse polarity
of
protection in
32
groups of 8
1.5 A
0.5 A
20 to 125 VDC 24 VDC
Yes
No
Yes
No
Yes
No
For variable
High packag‐
voltages
ing
density
16 outputs, isolated in groups of 8
125 VDC
230 VAC
-
SM 422;
SM 422;
DO 32xDC
DO 8xAC
24 V / 0.5 A
120/230 V/ 5 A
(-1FF00)
(-7BL00)
32 DO; isola‐
8 DO; isolated
ted in groups
in groups of 1
of
8
0.5 A
5 A
24 VDC
120/230 VAC
Yes
No
Yes
No
Yes
No
Particularly
For high cur‐
quick and with
rents with
interrupt capa‐
channel- spe‐
bility
cific isolation
SM 422; DO 16 x UC 30/230 V/Rel. 5 A
(-1HH00)
S7-400 Automation System Module Data
Reference Manual, Ausgabe 11/2016, A5E00850736-08
SM 422;
SM 422;
DO 16xAC
DO 16xAC
120/230 V/
20-120 V/ 2 A
2 A
(-5EH00)
(-1FH00)
16 DO; iso‐
16 DO; isola‐
lated in
ted in
groups of
groups of
4
1
2 A
2 A
120/230
20 to 120
VAC
VAC
No
Yes
No
Yes
No
Yes
-
For variable
currents
with chan‐
nel-specific
isolation

Hide quick links: