Siemens SIMATIC S7-400 Reference Manual page 320

Automation system module data
Hide thumbs Also See for SIMATIC S7-400:
Table of Contents

Advertisement

Analog modules
5.26 Analog output module SM 432; AO 8 x 13 Bit (6ES7432-1HF00-0AB0)
● for capacitive load
● for inductive load
Noise suppression for f = n (f1 ± 1%), (f1 = interfering frequency) n= 1.2 ...
● Common mode interference (UCM < AC 3 Vss / 50
Crosstalk between the outputs
Operational limit (in the entire temperature range, relative to output range)
● Voltage output
● current output
Basic error limit (operational limit at 25°C, relative to output range)
● Voltage output
● current output
Temperature error (relative to output range)
Linearity error (relative to output range)
Repeat accuracy (in settled state at 25 °C, relating to
output range)
Output ripple; bandwidth 0 to 50 kHz (relative to output
range)
Interrupts
Diagnostic functions
Substitute values can be connected
Output range (nominal values)
● Voltage
● Current
Load impedance (in rated range of output)
● at voltage outputs
320
Hz)
± 10 V
0 to 10 V
1 to 5 V
± 20 mA
4 to 20 mV
± 10 V
0 to 10 V
1 to 5 V
± 20 mA
0 to 20 mA
capacitive load
3.5 ms
0.5 ms
Noise suppression, error limits
> 60 dB
> 40 dB
± 0.5%
± 0.5%
± 0.5%
± 1%
± 1%
± 0.5%
± 0.5%
± 0.5%
± 0.5%
± 0.5%
± 0.02 % / K
± 0.05%
± 0.05%
± 0.05%
Status, interrupts, diagnostics
None
None
No
Data for selecting an actuator
± 10 V0 to 10 V1 to 5 V
± 20 mA
0 to 20 mA
4 to 20 mA
min. 1 kΩ
max. 1 µF
Reference Manual, Ausgabe 11/2016, A5E00850736-08
S7-400 Automation System Module Data

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents