PROFIBUS DP master interface IM 467/IM 467 FO
8.4 Specifications
8.4.2

Specifications of the IM 467 FO (6ES7467-5FJ00-0AB0)

Dimensions W x H x D (mm)
Weight
● Standard
● Transmission rate
● Transmission technology
Current consumption from the S7-400 bus (24 VDC)
The IM does not consume any current at 24 V, and it only makes
this voltage available at the MPI/DP interface.
Can be used in
IM 467 cannot be used with the CP 443-5
Supply voltage
Current consumption
● From 5 VDC
Addressing range
DP master
● DPV 1
● Enable/disable
Number of connectable I/O devices (slaves)
Number of connections for S7 functions for the programming
device and operator control and monitoring
Data volume per slave
Consistency
Configuration software
DP slave
● Different SSL IDs for system diagnostics
● Possibly extended SFC run times
● Additional return codes for SFC 14 and SFC 15
376
Dimensions and weight
PROFIBUS DP
Current consumption
PROFIBUS DP
Operating conditions
Deviations from the DP interface integrated in the CPU
25 x 290 x 210
700 g
PROFIBUS DP, EN 50 170
9.6 Kbps to 12 Mbps, configurable in
steps (3 Mbps and 6 Mbps not possi‐
ble)
FOC;
Wave length l = 660 nm 2 x duplex
sockets
Total current consumption of the com‐
ponents connected to the DP interfa‐
ces, with a maximum of 150 mA
SIMATIC S7-400, max. 4 IM 467 in
the central rack
5 VDC via the backplane bus
1.3 A
Max. 4 KB for inputs and 4 KB for out‐
puts
Yes
No
No
96
32 + 1 diagnostic connection
Max. 244 bytes
Max. 128 bytes
STEP 7
No
S7-400 Automation System Module Data
Reference Manual, Ausgabe 11/2016, A5E00850736-08