Specifications; Specifications Of The Im 467 (6Es7467-5Gj02-0Ab0)) - Siemens SIMATIC S7-400 Reference Manual

Automation system module data
Hide thumbs Also See for SIMATIC S7-400:
Table of Contents

Advertisement

PROFIBUS DP master interface IM 467/IM 467 FO

8.4 Specifications

PROFIBUS DP
Figure 8-6
Bending radius for the fiber-optic cable
When placing the fiber-optic duplex core into the plug adapter and routing the cable, be sure
not to exceed the permissible bending radius of 30 mm. See also the installation guidelines
on fiber-optic cables in the SIMATIC NET PROFIBUS Networks manual.
8.4
Specifications
8.4.1

Specifications of the IM 467 (6ES7467-5GJ02-0AB0))

Dimensions W x H x D (mm)
Weight
● Standard
● Transmission rate
● Transmission technology
Current consumption from the S7-400 bus (24 VDC)
The IM does not consume any current at 24 V, and it only makes
this voltage available at the MPI/DP interface.
Can be used in
374
Receiver
R
Transmitter
T
Receiver
R
Transmitter
T
Inserting the fiber-optic cables into the IM 467 FO
Transmitter
Receiver
Dimensions and weight
PROFIBUS DP
Current consumption
PROFIBUS DP
Operating conditions
Reference Manual, Ausgabe 11/2016, A5E00850736-08
Grip
25 x 290 x 210
700 g
PROFIBUS DP, EN 50 170
9.6 Kbps to 12 Mbps, configurable in
steps
RS 485 via 9-pin sub D socket
Total current consumption of the com‐
ponents connected to the DP interfa‐
ces, with a maximum of 150 mA
SIMATIC S7-400, max. 4 IM 467 in
the central rack
S7-400 Automation System Module Data