Siemens SIMATIC S7-400 Reference Manual page 61

Automation system module data
Hide thumbs Also See for SIMATIC S7-400:
Table of Contents

Advertisement

3.8 Power supply modules PS 407 10A (6ES7407-0KA01-0AA0) and PS 10A R (6ES7407-0KR00-0AA0)
PS 407 10A and PS 407 10A R technical specifications
Dimensions W x H x D (mm)
Weight
Cable cross-section
Cable diameter
Input voltage
● Rated value
● Permitted range
Line frequency
● Rated value
● Permitted range
Rated input current
● With 120 V AC
● At 110 V DC
● At 230 V AC
● At 230 V DC
Inrush current
● At 230 V AC
● At 300 V DC
Leakage current
Output voltage
● Rated values
Output current
● Rated values
Protection class pursuant to IEC 60536
Overvoltage category
Pollution degree
Rated voltage U
0 < U
150 V < U
S7-400 Automation System Module Data
Reference Manual, Ausgabe 11/2016, A5E00850736-08
Dimensions, weight and cable cross-sections
e
≤ 50 V
e
≤ 300 V
e
50x290x217
1.36 kg
3x1.5 mm
(stranded wire with wire end ferrule with
2
insulating sleeve; use hose line only)
3 to 9 mm
Input variables
110/230 V DC
120/230 V AC
88 to 300 V DC
85 to 264 V AC
(wide range input)
50/60 Hz
47 to 63 Hz
0.9 A
1.0 A
0.5 A
0.5 A
Peak value 230 A, full width at half maximum
200 µs
peak value 63 A*, full width at half maximum 1 ms*
Peak value 230 A, full width at half maximum
200 µs
peak value 58 A*, full width at half maximum 1 ms*
< 3.5 mA
Output variables
5.1 V DC/24 V DC
5 V DC: 10 A
24 V DC: 1.0 A
Parameters
I, with protective conductor
II
2
Test voltage
700 V DC (secondary <-> PE)
2200 V DC (primary <-> secondary/PE)
Power supply modules
61

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents