Table 5-14
Representation of analog values in current measuring ranges 4 to 20 mA
System
118,515 % 32767
117,593 % 32512
117,589 % 32511
27649
100,000 % 27648
75 % 20736
0,003617 % 1
0 % 0
- 1
- 17,593 % - 4864
≤ - 17,596 %
32767
S7-400 Automation System Module Data
Reference Manual, Ausgabe 11/2016, A5E00850736-08
Dec.
Hex.
7FFF
22.96 mA
7F00
7EFF
22.81 mA
6C01
6C00
20 mA
5100
16 mA
1
4 mA + 578.7 nA
0
4 mA
FFFF
ED00
1.185 mA
7FFF
Current measuring range
4 to 20 mA
Overflow
Overshoot range
Nominal range
Undershoot range
Wire break