AIR-TO-WATER HEAT PUMP
temperature (outflow water or room air) according to the outdoor air temperature.
Value of code 23: Lower limit of the outdoor air temperature;
Value of code 24: Upper limit of the outdoor air temperature;
Function code 25: Setting temperature gap from target temperature of
Set the temperature gap from target temperature (outflow water or room air) in
cooling mode;
This value requires frequent On and Off of the unit.
Function code 26: Setting temperature gap from target temperature of heating
Setting the temperature gap from target temperature (outflow water or room air) in
heating mode;
This value requires frequent On and Off of the unit;
Function code 27: Setting temperature gap from target temperature of sanitary
Set the temperature gap from target water tank temperature in sanitary heating mode.
Target temperature
Set by user
Water tank temperature
Value of code 21

3.5 Set engineer function parameter

cooling operation
operation
heating operation
A
A: heating by heat pump
B: heating by water heater in tank
C: no heating
D: heating by water heater in tank
Sanitary water heating
D
B
C
15
CONTROL PANEL MENU