Sinclair GSH-60IRA Manual page 19

Air-to-water heat pump
Hide thumbs Also See for GSH-60IRA:
Table of Contents

Advertisement

AIR-TO-WATER HEAT PUMP
use when the out-door temperature is below the set value in code 20.
If code 10 is set as 2, full capacity of back-up heater in the indoor unit can be turned into
use when the out-door temperature is below the set value in code 20.
Function code 11 :Setting start date of disinfection operation
Value of function code 11 determines the date when disinfection mode is running. '0'
stands for Sunday, '1' for Monday ... and '6' for Saturday.
Function code 12 :Setting start time in 24 hours of disinfection operation
Value of function code 12 determines the time when the disinfection mode is
running. '00' stands for 0:00am, '01' for 01:00am... '22' for 22:00pm and '23' for
23:00pm.
Function code 13 :Metal Base(pedestal) heater
If code 13 is set as 0, the Metal Base(pedestal) heater will never be turned on;
If code 13 is set as 1, when the compressor started and the out-door temperature is
below 0℃, the Metal Base(pedestal) heater will be turned on; when the compress
or stopped or the out-door temperature is higher than 2℃, the Metal Base(pedestal)
heater will be turned off.
Function code 14 :Quantity of tank sensor
If code 14 is set as 1, there is only one temperature sensor on the sanitary water
tank;
If code 14 is set as 2, there are two temperature sensors on the sanitary water tank;
the one in the middle of the tank is for display( in the control panel),and the other
one is for control(control ON/OFF of the heat pump or electric heater);
Function code 15 :Tank equipment
If code 15 is set as 0, there is no sanitary water tank installed in the system. The
sanitary water heating and disinfection operation are in valid in the control Panel;
If code 15 is set as 1, sanitary water tank is installed in the system. The sanitary water
heating and disinfection operation are available in the control panel.
Function code 16 :Other thermal equipment
If code 16 is set as 0, there is no other thermal equipment connected to the tank.
If code 16 is set as 1, other thermal equipment(such as gas boiler, oil boiler
solar system) is connected to the tank(this tank must be two coil,one for heat pump
and the other for other thermal equipment);
Function code 17 :FCU equipment
If code 17 is set as 0, there is no FCU (FAN COIL UNIT) equipped in the water
system. In order to preventing condensation on the floor during cooling operation, the
setting value of the outflow water temperature can not be below 16℃. If code 17 is
13