2.4 Commissioning Parameter Setting

[Operation Instructions]
1.At the menu page, by touching "Commission" and then entering the correct password (000048) in the pop-up
window, the commissioning parameter page will be accessed, where the left side is for the function setting and the
right side is for the parameter setting, as shown in the figure below.
[Notes]
●At the commissioning parameter setting page, when the state of any function changes, the system will
automatically save this change and this change will remain upon power failure.
●Do not modify any commissioning parameter except the approved qualified servicemen, as it would give birth
to adverse effects to the unit.
No.
Item
1
Ctrl. state
2-Way
2
valve
Solar
5
setting
6
Water tank
7
Thermostat
Other
8
thermal
Optional
9
E-Heater
Remote
10
sensor
Commissioning Function Setting
Range
T-water out/T-room
Cool 2-Way valve, On/Off
Heat 2-Way valve, On/Off
With/Without
Without/With A/With B
Without/Air/Air+ hot water
On/Off
With/Without
Off/1/2
With/Without
Default
When "Remote sensor" is set to "With", it can
T-water out
be set to "T-room".
It will decide the status of the 2-way valve under
the "Cool" and "Cool + Hot water" modes.
Under "Cool" or "Cool + Hot water" mode,
Off
the status of the 2-way valve depends on this
setting. This setting is unavailable to heating
only units.
It will decide the status of the 2-way valve under
On
the "Heat" and "Heat + Hot water" modes
When the water tank is unavailable, this setting
will be reserved.
When it is set to "With", the solar kitting will work
Without
on its own.
When it is set to "Without", hot water by the
solar kitting is unavailable.
Unavailable to mini chillers.
"A" indicates the internal coils;
Without
"B" indicates the external plate type heat
exchanger.
This setting cannot be interchanged between
Without
"Air" and "Air+ hot water" directly but via
"Without" this option
Off
This setting is available to mini chillers.
Without
/
Off
/
When it set to "Without", and the "Ctrl. state" will
Without
be defaulted to be "T-water out".
16