AIR-TO-WATER HEAT PUMP
Setting temperature gap from
25
target
temperature
operation
Setting
temperature
target
26
temperature of heating operation
Setting
temperature
target
27
temperature of sanitary heating
operation

3.4 Function Set-up Description

Function code 1:Setting temperature selection
The unit can operate according to air temperature or outflow water temperature. The air
temperature or outflow water temperature can be selected as setting temperature.
Note: Air temperature as setting temperature is ONLY available when Remote Air Sensor
Connection is enabled and Function Code 18 is set as 01.
Function code 2:Forced operation
Forced Operation includes forced cooling and forced heating operation:
Forced cooling operation should be performed when additional refrigerant charge is
required.
To charge the refrigerant, the unit must run in Cool mode.
Forced cooling should be performed upon the first run(test run)and when out-door
temperature is lower than 10 ℃;
Forced heating should be performed upon the first run(test run)and when out-door
temperature is higher than 35 ℃;
Forced Operation instantly makes the unit working in Cool/Heat mode for 15 minutes.
Note: • Before setting the forced operation,please turn off the unit;
When the forced cooling/Heating operation is set,press ON/OFF button in the
control panel. The unit will start running.
Press ON/OFF button in the control panel again, forced operation mode will be
finished.
• After running 15 minutes under Forced Operation, the system will
automatically stop operating.
Function code 3 :Celsius/Fahrenheit switching
Temperature is displayed in Celsius or Fahrenheit.
Function code 4 :Thermostat control
/
of
cooling
gap
from
/
gap
from
/
11
CONTROL PANEL MENU
2~10℃(default:
3℃)
2~10℃(default:
3℃)
2~8℃(default:
3℃)