3.4.5 Parameter setting example

IMPORTANT
"Changing zero position (of the LCD) from clockwise to counter-clockwise"
Starting situation: the positioner is operating remote-controlled.
1. Cange over from the remote level to the operating level:
-
Press and hold
-
Wait until the countdown has run down from 3 to 0.
-
Release
2. Change over to the configuration level:
-
Simultaneously press and hold
-
In addition, briefly press
-
Wait until countdown from 3 to 0 has run down.
-
Release
-
conf
3. Change over to parameter group 3._:
-
Simultaneously press and hold
-
In addition 2 x briefly press
-
conf
-
Release
-
conf
4. Select parameter 3.2 "Zero position":
-
Press and hold
-
In addition, 2 x briefly press
-
conf
-
Release
41/18-77 EN
An overview of the parameter settings that can be changed via the front
panel keypad is found in Appendix A.
and
MODE
and
MODE
ENTER
ENTER
.
and
°
C
%
is displayed.
mA
°
C
%
is displayed.
mA
and
MODE
ENTER
°
C
%
is displayed.
mA
.
MODE
°
C
%
is displayed.
mA
.
MODE
Electro-pneumatic positioner TZIDC-110
simultaneously.
ENTER
. Mode 1.1 is reached and indicated.
and
.
.
and
MODE
ENTER
.
.
.
.
29