2. Connect the wires to the terminals
•
Remove approximately 6 mm of the insulation.
•
When connecting the bus lines, shutdown module, proximity switches or microswit-
ches, insert the wire ends from the left into the appropriate screw terminal and hand-
tighten the screws (access from above).
Fig. 19
Wiring diagram
24
Shutdown module
24V (20V...30V)
Microswitches
max. 24V, max. 2A
Proximity switches
Supply 5...11VDC
Signal L
<
1mA, H
>
2 mA
Fieldbus,
bus powered
9...32V
Electro-pneumatic positioner TZIDC-110
NO
NC
NO
NC
Keep cable shields as short
as possible and connect
to ground on both sides
41/18-77 EN