Influence of vibration
≤ +/-1 % up to 10 g and 80 Hz
Seismic requirements
Meets requirements of DIN/IEC 68-3-3 Class III for strong and strongest earthquakes
Influence of mounting orientation
No effect
Meets the requirements of the following directives
EMC Directive 89/336/EEC as of May 1989
EC Directive for CE conformity marking
Environmental capabilities
Ambient temperature
-40 °C to +85 °C for operation, storage and transport
-25 °C to +85 °C when using proximity switches SJ2-S1N (NO)
Relative humidity
Operational (with closed housing and air supply switched on):
95 % (annual average), condensation permissible
Transport and storage:
75 % (annual average), non-condensing
Case
Material/Protections
Aluminum, protection class IP 65 (NEMA 4X)
Surface/color
Electrostatic dipping varnish with epoxy resin, stove-hardened
Case varnished black, RAL 9005, matt,
Cap Pantone 420
Electrical connections
Screw terminals:
2
max. 1.0 mm
for options, max. 2.5 mm
NOTICE: Do not expose the terminals to strain!
Cable entry
2 threads 1/2-14 NPT or M20x1.5
(1 with cable gland and 1 with pipe plug)
Pneumatic connections
Threads G 1/4 or 1/4-18 NPT
Weight
1.7 kg
Mounting orientation
any orientation allowed
Dimensions
see dimensional drawings in data sheet 10/18-0.23 EN
34
2
for bus connection
Electro-pneumatic positioner TZIDC-110
41/18-77 EN