Danfoss VLT HVAC Basic Drive FC 10 Quick Manual page 18

Table of Contents

Advertisement

Quick Guide
Motor Set-up
The Quick Menu Motor Set-up guides through the needed
motor parameters.
No & Name
Range
0-03 Regional
[0] Interna-
Settings
tional
[1] US
1-20 Motor
0.12-110kW/
power
0.16-150Hp
1-22 Motor
50.0 - 1000.0V
Voltage
1-23 Motor
20.0 - 400.0Hz
Frequency
1-24 Motor
0.01 -
Current
10000.00A
1-25 Motor
100.0 - 9999.0
Nominal Speed
RPM
4-12 Motor
0.0 - Hz
Speed Low
Limit [Hz]
4-14 Motor
0-HZ
Speed High
Limit [Hz]
3-41 Ramp 1
0.05 - 3600.0 s Size related
Ramp up time
3-42 Ramp 1
0.05 - 3600.0 s Size related
Ramp down
time
1-73 Flying
[0] Disabled
Start
[1] Enabled
VLT HVAC Basic Drive FC 101 Quick Guide
Default
Function
0
Size related
Enter motor
power from
nameplate data
Size related
Enter motor
voltage from
nameplate data
Size related
Enter motor
frequency from
nameplate data
Size related
Enter motor
current from
nameplate data
Size related
Enter motor
nominal speed
from nameplate
data
0.0 Hz
Enter the
minimum limit for
low speed
65
Ramp up time
from 0 to rated
motor frequency
par. 1-23
Ramp down time
from rated motor
frequency par.
1-23 to 0
0
Select Enable to
enable the drive
to catch a
spinning motor
®
MG.18.A1.02 - VLT
is a registered Danfoss trademark
Changes Made
Changes Made lists all parameters changed since factory
setting. Only the changed parameters in current edit-setup
are listed in changes made.
If the parameter's value is changed back to factory setting's
value from another different value, the parameter will NOT
be listed in Changes Made.
1.
Press [MENU] key to enter the Quick Menu until
indicator in display is placed above Quick Menu.
2.
Press [
] [
] to select either FC 101 wizard, closed
loop setup, motor setup or changes made, then
press [OK].
3.
Press [
] [
] to browse through the parameters in
the Quick Menu.
4.
Press [OK] to select a parameter.
5.
Press [
] [
] to change the value of a parameter
setting.
6.
Press [OK] to accept the change.
7.
Press either [Back] twice to enter "Status", or press
[Menu] once to enter "Main Menu".
The Main Menu accesses all parameters.
1.
Press [MENU] key until indicator in display is placed
above "Main Menu".
2.
Use [
] [
] to browse through the parameter
groups.
3.
Press [OK] to select a parameter group.
4.
Use [
] [
] to browse through the parameters in
the specific group.
5.
Press [OK] to select the parameter.
6.
Use [
] [
] to set/change the parameter value.
1
1
17

Advertisement

Table of Contents
loading

Table of Contents