 Auto 3 details
Auto 3 details
Outdoor temp setting to limit in cooling
Outdoor temp setting to limit in heating
Indoor temp switching to cooling
Indoor temp switching to heating
Select the item.
Set the outdoor temp settings to limit in
cooling and heating and the indoor temp
settings to limit in cooling and heating.
 Temp switching to cooling
Temp switching to cooling
Tap ▲▼ to set offset value.
Set the temperature switching to cooling
with Auto 1 and Auto 2.
The temperature can be set within the
range of 1 to 4 °C.
 Outdoor temp set for heating
Outdoor temp set for heating
Tap ▲▼ to set offset value.
Set the outdoor temperature for heating
with Auto 2 and Auto 3.
The temperature can be set within the
range of 10 to 22 °C.
"[Indoor temp, cooling] <
[Indoor return air temp]" and
"[Outdoor temp, cooling] <
[Outdoor air temp]"
36
⇒ Operation mode: Cooling
37
38
"[Indoor temp, heating] >
39
[Indoor return air temp]" and
"[Outdoor temp, heating] >
Back
[Outdoor air temp]"
⇒ Operation mode: Heating
 Temp switching to heating
Temp switching to heating
Tap ▲▼ to set offset value.
Set
Back
Set the temperature switching to heating
with Auto 1 and Auto 2.
The temperature can be set within the
range of 1 to 4 °C.
 Indoor temp set for cooling
Indoor temp set for cooling
Tap ▲▼ to set offset value.
Set
Back
Set the indoor temperature for cooling with
Auto 3.
Indoor temp, cooling: Can be set within the
range of 18°C to 30°C.
(Sample)
Forced thermo-OFF
Outdoor temp set for heatingSelection range
Outdoor temp
◆ The outdoor temp setting to limit in cooling is 19 °C, the outdoor temp setting to
limit in heating is 20 °C,
the indoor temp switching to cooling is 18 °C, and the indoor temp switching to
cooling is 25 °C.
Set
Back
Set
Back
−26−
Outdoor temp set for cooling Selection range
Cooling opera-
tion
Heating
operation
Forced thermo-OFF
 Outdoor temp set for cooling
Outdoor temp set for cooling
Tap ▲▼ to set offset value.
Set the outdoor temperature for cooling
with Auto 2 and Auto 3.
The temperature can be set within the
range of 10 to 30 °C.
 Indoor temp set for heating
Indoor temp set for heating
Tap ▲▼ to set offset value.
Set the indoor temperature for heating with
Auto 3.
The temperature can be set within the
range of 10 to 30 °C.