Alarm module

Alarm module
3 digital output circuits (terminals 31/32, 41/42, 51/52)
● Auxiliary voltage U
H
● Signal status
Low
High
● For connecting to circuits with the
following peak values
1 digital input circuit (terminals 11/12; electrically isolated from the basic device)
● Signal status
Low
High
● For connecting to circuits with the
following peak values
● Input voltage
● Input resistance
● Static destruction limit
Galvanic isolation
1 switching contact input (terminals 21/22; galvanically connected with basic device, can only be connected to floating
contact)
● Signal status
Low
High
● Contact load
32
Without explosion protection
6DR6003-8A
< DC 35 V
Disabled, I
< 300 µA
R
Conductive
Max. 50 mA permitted
Terminal voltage < 3 V; short-circuit-
proof
-
-
< ±35 V
±35 V
The three outputs DO 1, DO 2, DO 3; the input DI 2 (only terminals 11/12) and
the basic device are galvanically separated from each other.
With explosion protection Ex "ia", "ic",
"nA"
6DR6003-6A
4 ... 9.5 V (terminal voltage)
< 1.2 mA
1)
> 2.1 mA
1)
"ia"/"ic":
U
= 15.5 V
i
I
= 25 mA
i
P
= 64 mW
i
C
= 16 nF
i
L
= 78 µH
i
"nA"/"tb":
U
= 15,5 V
n
I
= 25 mA
n
≤ 4.5 V or open
> 13 V
"ia"/"ic":
U
= 25.2 V
i
I
= 155 mA
i
P
= 1 W
i
C
= 5 nF
i
L
= negligible
i
"nA"/"tb":
U
= 25.2 V
n
-
> 16 kΩ
-
Floating contact, open
Floating contact, closed
< 3 V, < 15 μA
SITRANS VP300 (6DR63..)