7.4.4

FOUNDATION Fieldbus communication

Communication group and
class
Function blocks
Execution times of the blocks
Physical layer profile
FF registration
Device address
7.5

Option modules

7.5.1

Alarm module

Alarm module
3 binary output circuits
● Alarm output A1: Terminals 41 and 42
● Alarm output A2: Terminals 51 and 52
● Fault message output: Terminals 31 and 32
● Auxiliary voltage U
H
● Signal status
High (not addressed)
Low *) (addressed)
*) The status is also Low if the
basic device is faulty or without
a auxiliary power.
● For connecting to circuits with the
following peak values
1 binary input circuit
● Binary input BE2: Terminals 11 and 12, terminals 21 and 22 (jumper)
● Galvanically connected with the
basic device
Signal status 0
Signal status 1
Contact load
● Electrically isolated from the
basic device
42
According to the technical specification of the Fieldbus Foundation for H1 communication
Group 3, Class 31PS (Publisher Subscriber)
1 resource block (RB2)
1 analog output function block (AO)
1 PID function block (PID)
1 transducer block (standard advanced positioner valve)
AO: 60 ms
PID: 80 ms
123, 511
Tested with ITK 5.0
22 (when delivered)
Without Ex protection/
with Ex protection Ex d
6DR4004-8A
≤ 35 V
Conductive, R = 1 kΩ,
+3/-1 % *)
Deactivated, I
< 60 µA
R
*) When using in the
flameproof housing, the
current consumption must
be restricted to 10 mA per
output.
-
With Ex protection Ex "ia"
6DR4004-6A
-
≥ 2.1 mA
≤ 1.2 mA
Switching thresholds for
supply as per EN 60947-
5-6:
U
= 8.2 V, R
= 1 kΩ
H
i
U
= DC 15.5 V
i
I
= 25 mA
i
P
= 64 mW
i
C
= 5,2 nF
i
L
= negligibly small
i
Floating contact, open
Floating contact, closed
3 V, 5 μA
With Ex protection
Ex "ic", "nA", "t"
6DR4004-6A
-
≥ 2.1 mA
≤ 1.2 mA
Switching thresholds for
supply as per EN 60947-
5-6:
U
= 8.2 V, R
= 1 kΩ
H
i
"ic":
U
= DC 15.5 V
i
I
= 25 mA
i
C
= 5,2 nF
i
L
= negligibly small
i
"nA"/"t":
U
≤ DC 15.5 V
n
SIPART PS2 (6DR5...)