3. Press
twice. The display shows the following:
4. Set the language for the display using
or
. The preset language is English.
5. Confirm the selection with
. The defined language is displayed.
The language for the display is set. The language setting must only be made once.
6. Switch to the measurement view by pressing the
button until the display shows the following:
7. Move the actuator alternately to both endstops using
and
.
8. Adhere to the action in the position feedback. If no fault message is shown when moving the actuator, you have fixed the
positioner correctly.
Result
The positioner is ready for commissioning.

Autom. initialization

Requirement
You have prepared the positioner for commissioning, as described in section "Preparing for commissioning (Page 23)".
Procedure
In order to initialize the positioner automatically, proceed as follow:
1. To change from the measurement view into the navigation view, press
. You are in the "1 Quick Start" main menu.
2. Click
four times. The display shows the following:
3. Select the actuator type with
or
SITRANS VP300 (6DR63..)
24
A5E03359515-01, 03/2011