Mounting the positioner on a part-turn actuator with OPOS interface (VDI/VDE 3847)

Requirement
Mounting surface may not exceed a surface roughness of Rz10 and a flatness deviation of 0.05 mm.
Description
s
Dimensions = mm (inches)
Magnet clamp fixing screw
Magnet clamp (contains magnet for contactless measurement of position)
Device fixing screws
Figure 5
Gap dimensions, position of the magnet clamp
Procedure
1. Prior to mounting the positioner, remove the cover foil from the pneumatic connections.
2. Screw magnet clamp
for OPOS interface (VDI/VDE 3847) (Page 11)".
3. Fasten the positioner on the interface. Tighten fixing screws
dimensions specified in the above figure.
4. Check whether the gap dimensions for the magnet clamp

Mounting kits

The description is supplied with the relevant mounting kit, and does not form a part of these operating instructions.
SITRANS VP300 (6DR63..)
A5E03359515-01, 03/2011
into the M6 threaded hole on the drive axis of the actuator, see picture in section "Dimensions
with a torque of 8 Nm. This will result set the gap
are correct.