Electric Connection - Siemens SITRANS VP300 Operating Instructions Manual

Electropneumatic positioner
Hide thumbs Also See for SITRANS VP300:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
Connection

Electric connection

Basic safety instructions
WARNING
Improper power supply
Danger of explosion in hazardous areas as result of incorrect power supply, e.g. using direct current instead of alternating
current.
● Connect the device in accordance with the specified power supply and signal circuits. The relevant specifications can
be found in the certificates, in Chapter "Technical data (Page 27)" or on the nameplate.
WARNING
Unsafe extra-low voltage
Danger of explosion in areas subject to explosion hazard due to voltage flashover.
● Connect the device to an extra-low voltage with safe isolation (SELV).
WARNING
Connecting device in energized state
Danger of explosion in areas subject to explosion hazard.
● Connect devices in hazardous areas only in a de-energized state.
Exceptions:
● Circuits of limited energy may also be connected in the energized state in hazardous areas.
● Exceptions for type of protection "Non-sparking nA" (Zone 2) are regulated in the relevant certificate
WARNING
Lack of equipotential bonding
Danger of explosion through compensating currents or ignition currents through lack of equipotential bonding.
● Ensure that the device is potentially equalized.
Exception: It may be permissible to omit connection of the equipotential bonding for devices with type of protection
"Intrinsic safety Ex i".
WARNING
Unprotected cable ends
Danger of explosion through unprotected cable ends in hazardous areas.
● Protect unused cable ends in accordance with IEC/EN 60079-14.
CAUTION
Condensation in the device
Damage to device through formation of condensation if the temperature difference between transportation or storage and
the mounting location exceeds 20 °C (68°F).
● Before taking the device into operation let the device adapt for several hours in the new environment.