In Case Of Adopting External Braking Resistor (Optional - Toshiba VF-PS1 Instruction Manual

Totally enclosed box type inverter
Hide thumbs Also See for VF-PS1:
Table of Contents

Advertisement

VFPS1-4300PLE~4900PLE
A switch or switches enable to reduce grounding capacitance.
*2: VFPS1-4300PLE have two switches.
⇒ For details, refer to main circuit terminal
VFPS1-4007PDE~4220PDE
There is no switch.
VFPS1-4300PDE~4900PDE
A switch enables to reduce grounding capacitance.

1.3.4 In case of adopting external braking resistor (Optional)

To wire for external braking resistor, an attention is needed because PA/+ terminal have a wiring to the internal DC
reactor. Refer to followings when you wire for external braking resistor.
0.75~22kW
With reference of the figure right, make the each
solderless terminal in back to back and fasten
them with the screw.
30~90kW
Fasten with the screw both of copper bar connected to the PA/+ terminal and the stripped cable for external braking
resistor.
Large Small
*2
Large Small
Large Small
Large Small
A-13
To change the capacitance
from small to large, push in
the button.
(Factory default position)
To change the capacitance
from large to small, pull up
the button.
To change the capacitance
from small to large, slide the
switch in direction shown left.
(Factory default position)
To change the capacitance
from large to small, slide the
switch in direction shown left.
PA/+ terminal screw
Wiring to the internal
DC reactor
Wiring to the external
braking resistor
E6581429