Vertical Terminations; Rigid Pipe 4" X 6-5/8 - Regency Horizon HZ40E Owners And Installation Manual

Hide thumbs Also See for Horizon HZ40E:
Table of Contents

Advertisement

installation
|
32

VERTICAL TERMINATIONS

"

RIGID PIPE 4" X 6-5/8

Two 45
elbows equal to one 90
o
Vent must be supported at ofsets.
Minimum distance between elbows is 1 ft. (305mm).
Maintain clearances to combustibles as listed in the "Clearances" section.
Horizontal vent must be supported every 3 feet.
Firestops are required at each loor level and whenever passing through a wall.
Must use optional rigid pipe adaptor (Part# 510-994) when using rigid pipe vent systems.
Vertical Venting with Two (2) 90
One 90
Option
V
A)
1' Min. 4' Max.
B)
2' Min. 5' Max.
C)
3' Min. 6' Max.
D)
4' Min. 7' Max.
E)
5' Min. 8' Max.
Regency Horizon ® HZ40E-10 Gas Fireplace
32 |
elbow. Maximum of four 45
o
o
Elbows
o
elbow = Two 45
o
elbows.
With these options,
H
V + V1
maximum total pipe
2' Min.
length is 30 feet with
minimum of 6 feet total
3' Min.
vertical and maximum 8
feet total horizontal.
4' Min.
5' Min.
Please note minimum
1 foot between 90
elbows is required.
6' Min.
Restrictor Position - Set 0 (factory setting)
elbows allowed, not including the starting 45
o
Vertical Venting with Two (2) 90
Option
H + H1
A)
2' Max.
B)
3' Max.
C)
4' Max.
D)
5' Max.
o
E)
6' Max.
For additional vertical venting with
2 x 90
elbows, refer to "Rigid Pipe
o
Venting Arrangements" Section.
elbow at the lue collar.
o
o
Elbows
o
o
One 90
elbow = Two 45
elbows.
With these options, maximum
V
total pipe length is 30 feet
2' Min.
with minimum of 6 feet total
vertical and maximum 6 feet
3' Min.
total horizontal.
4' Min.
Please note minimum 1
5' Min.
foot between 90
required.
6' Min.
Restrictor Position - Set 0 (factory setting)
o
elbows is