Micromaster 420 Fault Codes; Table 6-2 Micromaster 420 Fault Codes - Siemens Micromaster 420 Operating Instruction

Hide thumbs Also See for Micromaster 420:
Table of Contents

Advertisement

International English
6.3

MICROMASTER 420 fault codes

In the event of a failure, the inverter switches off and a fault code appears on the display.
Table 6-2
Fault Code
F0001
Overcurrent
F0002
Overvoltage
F0003
Undervoltage
F0004
Inverter
Overtemperature
F0005
Inverter I
F0011
Motor Overtemperature
2
I
F0041
Stator resistance
measurement failure
94
MICROMASTER 420 Fault Codes
Description
1. Motor power does not
correspond to the inverter
power.
2. Motor lead short circuit
3. Earth fault
Supply voltage out of tolerance
load is regenerating.
Mains supply removed when
inverter is running.
Ambient temperature outside of
limits,
Fan failure
2
T
Inverter is overloaded
1. Motor overloaded.
T
2. Motor data incorrect.
3. Check parameter for motor
thermal time constant.
4. Check parameter for motor I
warning level.
5. Long time period operating at
low speeds
Stator resistance measurement
failure
Possible Causes
2
t
6. TROUBLESHOOTING
Diagnosis & Remedy
1. Check whether the motor power
corresponds to the inverter
power.
2. Check that the cable length limits
have not been exceeded.
3. Check motor cable and motor for
short-circuits and earth faults.
4. Check whether the motor
parameters correspond with the
motor being used.
5. Check the stator resistance
(P0350).
6. Increase the ramp-up-time
(P1120).
7. Reduce the boost set in (P1310),
(P1311) and (P1312).
8. Check whether the motor is
obstructed or overloaded.
1. Check whether the supply voltage
is within the limits indicated on the
rating plate.
2. Check if dc-link voltage
controller (P1240) is enabled and
parameterized correctly.
3. Increase the ramp-down time
(P1121).
1. Check whether the supply voltage
is within the limits indicated on the
rating plate.
2. Check the supply is not subject to
temporary failures or voltage
reductions.
1. Check that the integral fan rotates
when drive is running.
2. Check if pulse frequency is set to
default value.
3. Ambient temperature could be
higher than specified for the
inverter.
4. Check that air inlet and outlet
points are not obstructed.
1. Check if load duty-cycle is within
specified limits.
2. Check that motor power
corresponds to inverter power
1. Check motor data.
2. Check loading on motor.
3. Boost settings too high (P1310,
P1311, P1312)
1. Check if the motor is connected to
the inverter
2. Check that the motor data has
been entered correctly.
MICROMASTER 420 Operating Instructions
6SE6400-5AA00-0BP0