5. SYSTEM PARAMETERS
Parameter
Number
r0052
CO/BO: Status word 1
This parameter displays the first active status word of the inverter (bit format) and can be
used to diagnose inverter status. A description of the Status word display segments is
given in the Parameter Introduction and can be interpreted as follows.
Possible values:
Bit 0
Drive ready
Bit 1
Drive ready to run
Bit 2
Drive running
Bit 3
Drive fault active
Bit 4
OFF2 active
Bit 5
OFF3 active
Bit 6
Switch on inhibit active
Bit 7
Drive warning active
Bit 8
Deviation setpoint/actual value
Bit 9
PZD control (Process Data Control)
Bit A
Maximum frequency reached
Bit b
Warning: Motor overload factor
Bit C
Motor holding brake active
Bit d
Motor overload
Bit E
Motor running direction right
Bit F
Inverter overload
Notes:
The individual status bits can be configured to the digital output using P0731.
To enable the user to read the relevant parameter bits display, refer to the diagram below:
MICROMASTER 420 Operating Instructions
6SE6400-5AA00-0BP0
Parameter Name
.
-
@
+
>
%
$
#
"
!
0
NO
1
YES
0
NO
1
YES
0
NO
1
YES
0
YES
1
NO
0
YES
1
NO
0
YES
1
NO
0
NO
1
YES
0
NO
1
YES
0
YES
1
NO
0
NO
1
YES
0
NO
1
YES
0
YES
1
NO
0
YES
1
NO
0
YES
1
NO
0
NO
1
YES
0
YES
1
NO
)
'
&


International English
♦ ♦ ♦ ♦ P0003 User
Min
Access Level
Max
♦ ♦ ♦ ♦ P0004 Setting
[Default]
♦ ♦ ♦ ♦ Changeable
Units
♦ ♦ ♦ ♦ Status
-
2
-
7
[-]
-
51