5. SYSTEM PARAMETERS
Parameter
Number
r0754
Smoothed analog input value
Shows the smoothed value of the analog input in % after the characteristic block.
Note:
100% = 10V.
r0755
Analog input value normalized to 16384 (4000 Hexadecimal)
Displays the analog input, scaled using ASPmin and ASPmax.
Analog setpoint from the analog scaling function (See parameters P0757 to P0760) can
vary from ASPmin to ASPmax as shown in the associated diagram.
The largest magnitude (value without sign) of ASPmin and ASPmax defines the scaling of
16384.
Examples:
ASPmin = 300%, ASPmax = 100% then 16384 represents 300%. This parameter will vary
from 5461 to 16384
ASPmin = -200%, ASPmax = 100% then 16384 represents 200%. This parameter will vary
from –16384 to +8192
Note:
This value is used as an input to analog BICO connectors
P0756
Analog input monitoring
Enables analog input monitoring.
Possible settings:
0
=
1
=
When monitoring is enabled and a deadband is defined (P0761), a fault condition will be
generated (F0080) when the analog input voltage falls below 50% of the deadband voltage.
Note:
This function is disabled if the analog scaling block (see P0757 – P0760) is programmed to
output negative setpoints.
MICROMASTER 420 Operating Instructions
6SE6400-5AA00-0BP0
Parameter Name
Monitoring disabled.
Monitoring enabled
International English
♦ ♦ ♦ ♦ P0003 User
Min
Access Level
Max
♦ ♦ ♦ ♦ P0004 Setting
[Default]
♦ ♦ ♦ ♦ Changeable
Units
♦ ♦ ♦ ♦ Status
-
2
-
8
[-]
%
-
2
-
8
[-]
-
0
2
1
8
[0]
-
61