4.3 Hotel numbering mode

the number from the keyboard). This numbering mode is used for apartments of
numbers higher than 255.
logical number = physical number + range shift
This numbering mode is switched on in a moment of setting of parameter value
'range shift' to the value higher than '0'.
Example:
In a building an entry phone should be used for apartments Nos. 301...310.
In uniphones physical numbers should be programmed as follows: in apartment
301 number 1, in apartment 302 number 2 etc.
Then cassette programming mode should be entered (see item 8, page 27) and
the parameter of range shift should be set to value 300.
After having done this and selecting from a keyboard number 301 the uniphone in
which number 1 has been programmed will ring, after having selected number 302
uniphone with number 2 will ring etc.
4.3
Hotel numbering mode
This numbering mode is meant for the buildings in which room number starts
with a digit defining number of floor on which the room is located (hotels, resort
houses, dormitories etc.). Physical number of a uniphone is calculated according to
the formula:
where P - floor number, LL - amount of rooms on one floor (value of parameter
[LPi]) - see dwg. 30), XX - number of room on the floor – number from the range
1 ... [LPi]
This numbering mode will be activated at the moment of setting the value of
parameter [LPi] "amount of rooms on a floor" to value higher than zero.
Example:
An entry phone should be mounted in a five-storied building in which
the numbering system is as follows: on the ground floor 1 . . . 20, on the first floor
101 . . . 102 etc. There are 20 rooms on the ground floor. On next floors, after
taking into account full hundred numbers which are also taken into consideration
in calculations (100, 200, 300...) we get 21 numbers for each floor. First of all
the cassette programming mode should be entered and parameter [LPi] (amount
of rooms on the floor) should be set to value 21. After quitting the programming
mode the exchange operates in hotel numbering mode.
Then it should be defined which logical numbers will correspond to individual phys-
ical numbers of uniphones. To do this a formula or a calculator available in one
Physical number = P * LL + XX (A)
10
4 NUMBERING MODES