Function Setting

Function selection mode
In measurement mode, press the
(when using a product with unit selection function, [F 0] will be displayed).
The [F
] indicates the mode for changing each Function Setting.
Press the
button for 2 seconds or longer in function selection mode to return to measurement mode.

■Default settings

Item
[F 0]
[Uni] Unit selection function
[oU1] Output mode (OUT1)
[1ot] Reversed output (OUT1)
[P_1] Input of set value (OUT1)
[F 1]
[H_1] Setting of Hysteresis (OUT1)
[CoL] Display colour
[oU2] Output mode (OUT2)
[2ot] Reversed output (OUT2)
[P_2] Input of set value (OUT2)
[F 2]
[H_2] Setting of Hysteresis (OUT2)
[F 3]
[FLU] Operating fluid
[F 4]
[rEF] Reference condition
[F 5]
[eES] Response time
[F 6]
[dSP] Display mode
[F 7]
[inP] External input
[F 8]
[drE] Display resolution
[F 9]
[PrS] Auto-preset
[F10]
[EEP] Accumulated value hold
[F11]
[AFL] Analogue output filter
[F12]
[Eco] Power saving mode
[F13]
[Pin] Security code
[F98]
[ALL] Setting of all functions
[F99]
[ini] Reset to the default settings
button for 2 seconds or longer, to display [F 1].
Default setting
[
L] L/min
[HYS] Hysteresis mode
[1_P] Normal output
[
] 50% of maximums rated flow
PFM710: 5 L/min, PFM725: 12.5 L/min
PFM750: 25 L/min, PFM711: 50 L/min
[
] 3% of maximums rated flow
PFM710: 0.3 L/min, PFM725: 0.8 L/min
PFM750: 1.5 L/min, PFM711: 3 L/min
[SoG] ON: Green OFF: Red
[HYS] Hysteresis mode
[2_P] Normal output
[
] 50% of maximums rated flow
PFM710: 5 L/min, PFM725: 12.5 L/min
PFM750: 25 L/min, PFM711: 50 L/min
[
] 3% of maximums rated flow
PFM710: 0.3 L/min, PFM725: 0.8 L/min
PFM750: 1.5 L/min, PFM711: 3 L/min
[ A i r ] dry air, N
2
[ A n r ] Standard condition
[1.00] 1 second
[ i n S ] Instantaneous flow
[ r _ r ] Accumulated flow external reset
[1E2] 100-split
[oFF] Manual
[oFF] OFF
[ o n ] With filter
[oFF] Unused
[oFF] Unused
[oFF] Unused
[oFF] Unused
-22-
Page
Page
23
Page
24
Page
25
Page
27
Page
28
Page
29
Page
30
Page
31
Page
32
Page
35
Page
36
Page
38
Page
39
Page
40
Page
41
Page
42
Page
44
No.PF※※-OMJ0006-G

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents