5.1 Pre-wiring Warnings
Before wiring or making any electrical connection, make sure that the UPS is in
shutdown status, and the power supplied to the input and output of the UPS is
completely cut off to avoid accidents.
When connecting the UPS to the mains and the loads, you must install the pro-
tective devices. The protective devices must be approved components that meet
Capacity
6kVA
10kVA
Check that the size, diameter, phase, and polarity of each cable that needs to
connect to the UPS are correct. Please refer to
Table 5-2: Input/ Output Electrical Data
Capacity
Input Cable
Output Cable
Battery Cable
Input Breaker
NOTE :
1. Please install a suitable conduit and bushing to protect input/ output
wiring.
2. Please refer to local/ national electrical codes and local regulations for
acceptable non-fuse breakers and cable size.
3. Cables with PVC material and with temperature resistance up to
105°C are suggested.
Chapter 5 : Wiring
Protective Device
D Curve- 63A Breaker
D Curve- 80A Breaker
8AWG/ 6mm
8AWG/ 6mm
8AWG/ 6mm
63D (2-pole x 1)
Suggested Supplier
I/P: DELIXI (CDB6i1252D63)
O/P: DELIXI (CDB6i1252D63)
I/P: DELIXI (CDB6i1252D80)
O/P: DELIXI (CDB6i1252D80)
6kVA
2
2
2
27
Chapter 5
.
10kVA
2
6AWG/ 10mm
2
6AWG/ 10mm
2
6AWG/ 10mm
80D (2-pole x 1)
Wiring