Allen-Bradley SLC 500 Quick Start Manual page 62

Ethernet
Hide thumbs Also See for SLC 500:
Table of Contents

Advertisement

5–18
Using RS232-to-Ethernet Channel-to-Channel Passthru
SLC 5/05 #2 Message Setup
Channel is set to one for Ethernet.
Target Node is the DH485 node address of the SLC 5/03
destination processor.
Message Timeout for any Ethernet MSG cannot be modified in
the Ethernet Message Setup dialog box. It is assigned by the
processor, and is determined by adding the Channel 1 MSG
Connection Timeout to the MSG Reply Timeout, then adding 5
seconds. This value can be modified by changing one or both of
the timeout values in the Channel 1 channel configuration screen.
The modified message timeout applies to all MSG instructions.
The Remote Bridge Link ID is the Link ID of Channel 0 of the
SLC 5/05 #1 bridge.
The Remote Bridge Address is the DH485 address for Channel
0 of SLC 5/05 #1.
The Local Bridge Address is the IP address of the SLC 5/05 #1
bridge.
Publication 1747-10.4