Error Code
D4H
Connection not completed before user-specified timeout
D5H
Connection timed out by the network
D7H
Connection refused by destination host
D8H
Connection was broken
D9H
Reply not received before user-specified timeout
DAH
No network buffer space available
E1H
PCCC Description: Illegal Address format, a field has an illegal value.
E2H
PCCC Description: Illegal Address format, not enough fields specified.
E3H
PCCC Description: Illegal Address format, too many fields specified.
E4H
PCCC Description: Illegal Address, symbol not found.
E5H
PCCC Description: Illegal Address format, symbol is 0 or greater than the maximum number of characters supported
by this device.
E6H
PCCC Description: Illegal Address, address does not exist, or does not point to something usable by this command.
E7H
Target node cannot respond because length requested is too large.
E8H
PCCC Description: Cannot complete request, situation changed (file size, for example) during multi-packet operation.
E9H
PCCC Description: Data or file is too large. Memory unavailable.
EAH
PCCC Description: Request is too large; transaction size plus word address is too large.
EBH
Target node cannot respond because target node denies access.
ECH
Target node cannot respond because requested function is currently unavailable.
EDH
PCCC Description: Resource is already available; condition already exists.
EEH
PCCC Description: Command cannot be executed.
EFH
PCCC Description: Overflow; histogram overflow.
F0H
PCCC Description: No access
F1H
Local processor detects illegal target file type.
F2H
PCCC Description: Invalid parameter; invalid data in search or command block.
F3H
PCCC Description: Address reference exists to deleted area.
F4H
PCCC Description: Command execution failure for unknown reason; PLC-3 histogram overflow.
F5H
PCCC Description: Data conversion error.
F6H
PCCC Description: The scanner is not able to communicate with a 1771 rack adapter. This could be due to the
scanner not scanning, the selected adapter not being scanned, the adapter not responding, or an invalid request of a
"DCM BT (block transfer)".
F7H
PCCC Description: The adapter is not able to communicate with a module.
F8H
PCCC Description: The 1771 module response was not valid – size, checksum, etc.
F9H
PCCC Description: Duplicated Label.
FAH
Target node cannot respond because another node is file owner (has sole file access).
FBH
Target node cannot respond because another node is program owner (has sole access to all files).
FCH
PCCC Description: Disk file is write-protected or otherwise inaccessible (off-line only).
FDH
PCCC Description: Disk file is being used by another application; update not performed (off-line only).
FFH
Local communication channel is shut down.
Note:
For 1770–6.5.16 DF1 Protocol and Command Set Reference Manual Users:
The MSG error code reflects the STS field of the reply to your MSG instruction.
Codes E0–EF represent EXT STS codes 0–F.
Codes F0–FD represent EXT STS codes 10–1D.
Communicating on the Ethernet Network
Description of Error Condition
4–7
Publication 1747-10.4