Using RS232-to-Ethernet Channel-to-Channel Passthru
5–9
SLC 5/05 #2 Message Setup
Channel is set to 1 for Ethernet.
Message Timeout for any Ethernet MSG cannot be modified in
the Ethernet Message Setup dialog box. It is assigned by the
processor, and is determined by adding the Channel 1 MSG
Connection Timeout to the MSG Reply Timeout, then adding 5
seconds. This value can be modified by changing one or both of
the timeout values in the channel 1 channel configuration screen.
The modified message timeout applies to all MSG instructions.
The Remote Bridge Link ID is the Link ID of Channel 0 of the
SLC 5/05 #1 bridge.
The Remote Bridge Address is zero, since the SLC 5/05 #1, as
the bridge, is always node or Source ID 0 for its DF1 channel.
The Local Bridge Address is the IP address of the SLC 5/05 #1
bridge.