Jumper Settings - Daikin FTKS20CVMB Service Manual

Inverter pair wall mounted type c-series
Hide thumbs Also See for FTKS20CVMB:
Table of Contents

Advertisement

SiBE04-401
1.2

Jumper Settings

1.2.1 When Two Units are Installed in One Room
When two indoor units are installed in one room, the two wireless remote controllers can be set
for different addresses.
How to set the different addresses
(1) Remove the front grille. (3 screws)
(2) Remove the electrical box (1-screw).
(3) Remove the drip proof plate. (4 tabs)
(4) Cut the address jumper
(1) Slide the front cover and take it off.
(2) Cut the address jumper J4.
1.2.2
Jumper Setting
(On indoor control PCB)
Others
Control PCB of the indoor unit
JA
Wireless remote controller
Jumper
Function
JC
Power failure
recovery function
JB
Fan speed setting
when compressor is
OFF on thermostat.
on the control PCB.
(R2871)
When connected
(factory set)
Auto-restart
Fan speed setting
Remote controller
setting
(R2872)
When cut
Unit does not resume operation
after recovering from a power
failure. Timer ON-OFF settings
are cleared.
;
Fan rpm is set to "0"
<Fan stop>
Others
205

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents